RCT 3000VA On-Line Tower UPS (RCT-3000-WPTU)
Capacity
3000 VA / 2400 W
Input
Voltage
100/110/115/120/127 VAC or 200/208/220/230/240 VAC
Voltage Range
55-150 VAC or 110-300VAC @ 50% Load, 85-140 VAC or 160-280 VAC @ 100% load
Frequency Range
40 Hz ~ 70 Hz
Power Factor
? 0.99 @ nominal voltage (100% load)
Output
Output Voltage
100/110/115/120/127 VAC or 200/208/220/230/240 VAC
AC Voltage Regulation (Batt. Mode)
ñ1%
Frequency Range (Synchronized Range)
47~53 Hz or 57~63 Hz
Frequency Range (Batt. Mode)
50 Hz ñ 0.25 Hz or 60 Hz ñ 0.3 Hz
Current Crest Ratio
3:1 (max.)
Harmonic Distortion
? 3 % THD (Linear Load) ; ? 6 % THD (Non-linear Load)
Transfer Time
AC Mode to Batt. Mode
Zero
Inverter to Bypass
4 ms (Typical)
Waveform (Batt. Mode)
Pure Sine Wave
Efficiency
AC Mode
90 %
Battery Mode
88%
Battery
Standard Model
Battery Type
12 V / 9 Ah
Numbers
6
Typical Recharge Time
4 hours recover to 90% capacity
Charging Current (max.)
1 A
Charging Voltage
82.1 VDC ñ 1%
Long-run Model
Battery Type
Depending on the applications running
Numbers
6ÿÿ ÿ8
Charging Current (max.)
1A/2A/4A/6A (Adjustable)
Charging Voltage
82.1 VDC ñ 1%ÿÿ ÿ109.4 VDC ñ 1%
Indicators
LCD Display
UPS Status, Load Level, Battery Level, Input/Output Voltage, Discharge timer and Fault conditions
Alarm
Battery Mode
Sounding every 4 seconds
Low Battery
Sounding every second
Overload
Sounding every twice second
Fault
Continuously Sounding
Physical
Standard Model
Dimensions, D X W X H(mm)
421ÿ x 190 x 318
Net Weight (kgs)
27.6
Long-run Model
Dimensions, D X W X H(mm)
391ÿ x 145 x 220
Net Weight (kgs)
7.4
Environment
Humidity
20-90 % RH @ 0- 40ø (non-condensing)
Noise Level
Less than 50dB @ 1 meter
Management
Smart RS-232 and USB
Supports Windows© 2000/2003/XP/Vista/2008. Windows© 7/8, Linus and MAC
Optional SNMP
Power management from SNMP manager and web browser