RCT 6000VA On-Line Tower UPS (RCT-6000-WPTU)
6000 VA / 4800 W
Input
Voltage
208/220/230/240 VAC
Voltage Range
110-300VAC @ 50% Load, 176-300VAC @ 100% load
Frequency Range
46~54 Hz or 56~64 Hz
Power Factor
? 0.99 @ nominal voltage (100% load)
Output
Output Voltage
220/230/240 VAC
AC Voltage Regulation (Batt. Mode)
ñ1%
Frequency Range (Synchronized Range)
46~54 Hz or 56~64 Hz
Frequency Range (Batt. Mode)
50 Hz ñ 0.1 Hz or 60 Hz ñ 0.1 Hz
Current Crest Ratio
3:1 (max.)
Harmonic Distortion
? 3 % THD (Linear Load) ; ? 5 % THD (Non-linear Load)
Transfer Time
AC Mode to Batt. Mode
Zero
Inverter to Bypass
Zero
Waveform (Batt. Mode)
Pure Sinewave
Efficiency
AC Mode
92 %
Battery Mode
90%
Battery
Standard Model
Battery Type
12 V / 9 Ah
Numbers
16
Typical Recharge Time
9 hours recover to 90% capacity
Charging Current (max.)
1 A / 2 A
Charging Voltage
218.4 VDC ñ 1%
Long-run Model
Battery Type
Depending on the applications running
Numbers
16~20 (Adjustable)
Charging Current (max.)
1A/2A/4A/6A (Adjustable, 6A is only available for 16pcs batteries)
Charging Voltage
218.4 VDC ñ 1% (Based on 16pcs Batteries)
Indicators
LCD Display
UPS Status, Load Level, Battery Level, Input/Output Voltage, Discharge timer and Fault conditions
Alarm
Battery Mode
Sounding every 4 seconds
Low Battery
Sounding every second
Overload
Sounding every twice second
Fault
Continuously Sounding
Physical
Standard Model
Dimensions, D X W X H(mm)
369ÿ x 190 x 688
Net Weight (kgs)
61
Long-run Model
Dimensions, D X W X H(mm)
369ÿ x 190 x 318
Net Weight (kgs)
12
Environment
Humidity
0-95 % RH @ 0- 50ø (non-condensing)
Noise Level
Less than 55dB @ 1 meter
Management
Smart RS-232 and USB
Supports Windows© 2000/2003/XP/Vista/2008. Windows© 7/8, Linus and MAC
Optional SNMP
Power management from SNMP manager and web browser